ISO 50001 energy review: how to analyse energy use and select significant energy uses (clause 6.3)

The energy review is the analysis every ISO 50001 system is built on. What clause 6.3 requires, how to select significant energy uses on written criteria, a worked example from a food factory, when to update the review and what auditors check.

  • Updated September 2026
  • 8-minute read
  • Part of the ISO 50001 hub

Key points

  • The ISO 50001 energy review (clause 6.3) is the analysis the whole energy management system stands on: where energy goes, which uses matter most, what drives them and where the savings are.
  • It has five parts: analyse use and consumption from measured data, identify the significant energy uses, profile each one, rank the opportunities and estimate future consumption.
  • Significant energy uses are chosen against criteria you write down, on two tests: a substantial share of consumption, or considerable potential for improvement.
  • The review is never finished. It is updated at intervals you define and whenever facilities, equipment, systems or energy-using processes change in a major way.

What does the ISO 50001 energy review require?

The ISO 50001 energy review is a structured analysis of how an organisation uses energy, carried out on measured data, that identifies its significant energy uses (SEUs) and the opportunities to improve energy performance. It sits in clause 6.3 of ISO 50001:2018 and feeds the objectives, indicators, baseline, operating criteria and data collection plan.

The 2018 edition reads as a sequence: you look at all the energy first, narrow down to the uses that count, understand each of those in detail, then turn what you learned into ranked opportunities and a view of what consumption will look like next year. A tidy SEU list with no analysis behind it is a finding waiting to happen.

What the review does not do is set the indicators or the baseline. Those belong to clauses 6.4 and 6.5, covered in EnPIs, energy baselines and normalisation; the review supplies the data and the relevant variables they are built on.

The five parts of the energy review

Part of 6.3The question it answersWhat you keep
Analyse energy use and consumptionWhich energy types do we use, how much, and on what?A breakdown by energy type, site and use, based on invoices, meters and justified estimates
Identify significant energy usesWhich uses account for most of the energy, or offer most of the improvement?Written selection criteria and the SEU list that results from applying them
Profile each SEUWhat drives it, how well is it performing now, and whose work affects it?Relevant variables, current energy performance and the roles or people named for each SEU
Determine and prioritise opportunitiesWhere can energy performance improve, and what comes first?An opportunities register with estimated savings, cost and effort, and a ranking
Estimate future use and consumptionWhat will consumption look like over the coming period?A forecast that takes planned production, occupancy, weather and projects into account

How do you analyse energy use and consumption?

Start with the invoices: twelve months or more of invoices for electricity, gas, fuel oil, steam, LPG, diesel for vehicles and any other energy type inside the boundary give totals by carrier. Scope matters here: ISO 50001 does not allow an energy type inside the scope and boundaries to be left out, so a fleet or a standby generator counts if it sits inside them.

Next, split the totals by use. Main meters and existing sub-meters do some of the work; the rest comes from engineering estimates, such as rated power multiplied by run hours and a load factor, or a short logging campaign on a compressor or a chiller. What an auditor will question is a breakdown that adds up to more, or less, than the invoices say.

The output is a consumption map: for each site and energy type, the main uses and their approximate share. Keep the arithmetic visible, so next year's questions are answered by the workbook rather than one engineer's memory. Metering gaps are closed by the data collection plan, explained in The energy data collection plan and metering.

How are significant energy uses selected?

ISO 50001 defines a significant energy use as one that accounts for substantial energy consumption, offers considerable potential for improvement, or both. The standard sets no percentage. You decide the criteria, write them down and apply them the same way every time the review is updated.

Good criteria combine both tests. A consumption threshold catches the big loads; an opportunity test catches a badly controlled smaller use. A useful practical rule is that every SEU must be something a named person can influence through operation, maintenance or purchasing, because clause 6.3 asks you to identify the people whose work affects each one.

Profiling each SEU

For every SEU, record three things. The relevant variables are the factors that genuinely drive consumption, such as tonnes produced, degree days, occupied rooms or operating hours; they are tested later with data, not assumed. Current energy performance is today's position, often a specific consumption per unit of output. The people are the operators, maintenance technicians, shift leaders or contractors whose decisions change the result, and they become the audience for competence and awareness under clause 7.

How Sterling runs the energy review

The review is built with your engineers, from your own data.

Sterling's expert and experienced consultants sit with the people who run the plant or the buildings, work through invoices and meter data, agree the selection criteria with you and test the relevant variables before any indicator is set. The method, the SEU list and the opportunities register live in Effivity from the first workshop, so the next update starts from the last one. We ensure successful certification for our clients.

Book a free discovery call

A worked example: a single-site food factory

Consider a factory that uses electricity and natural gas. The figures below are illustrative, to show the method, and are not benchmarks for any sector. The energy team agreed two criteria: any use above ten per cent of total site energy is an SEU, and any smaller use with a clear, low-cost improvement is added on the opportunity test.

Energy useShare of site energyRelevant variables testedDecision
Steam boilers (gas)About 38%Tonnes produced, product mixSEU on consumption
Refrigeration and cold storesAbout 24%Tonnes produced, outdoor temperatureSEU on consumption
Compressed airAbout 11%Production hoursSEU on consumption; leaks noted as an opportunity
Office and warehouse HVACAbout 6%Degree days, occupied hoursSEU on opportunity: runs at weekends
Lighting and small powerAbout 5%Operating hoursNot an SEU; covered by general awareness

Four SEUs now carry about 79% of site energy. The opportunities register ranks a leak survey on compressed air first (low cost, quick), then condensate return on the boilers, then scheduling of the HVAC. The future estimate uses next year's production plan and a normal weather year, and it becomes the reference for comparing actual with expected consumption under clause 9.1.

When must the energy review be updated, and what is the record?

Two triggers apply. The first is a defined interval that you set; annually is a practical choice because it lines up with the management review. The second is a major change in facilities, equipment, systems or energy-using processes: a new production line, a building extension, a switch from gas to electric heating, or a site closure. Define what counts as major in advance.

The record has two layers. One is the method: the data sources, the estimating rules, the SEU criteria and how opportunities are ranked. The other is the result of each review: the consumption breakdown, the SEU list with variables, current performance and people, the ranked opportunities and the forecast. Keep earlier versions. At recertification the auditor will ask how the picture changed.

When an update changes the SEUs or their variables, check the knock-on effects the same day: indicators and baselines, operating criteria, the data collection plan and training needs may all move with it.

Common mistakes in the energy review

  • SEUs chosen by convenience. The uses that already have meters are picked, while the unmetered boiler house is left out. Criteria first, metering second.
  • Variables assumed, never tested. Production is named as the driver of every SEU without checking the data. Some loads follow the weather or the calendar instead.
  • No names against SEUs. The clause requires the people whose work affects each one; a blank column shows up in competence and awareness later.
  • A one-off exercise. The review was done for the certification project and never updated after the new line was installed.

For the full set of ISO 50001 requirements around the review, see the ISO 50001 requirements guide.

ISO 50001 energy review: questions buyers ask

Is the ISO 50001 energy review the same as an energy audit?

No, although they overlap. An energy audit, as described in ISO 50002-1, is a detailed study of a site or process that often feeds the review; the energy review is a standing part of the management system, repeated at defined intervals, and it drives the SEUs, indicators and action plans.

Can an external consultant carry out the energy review for us?

An external consultant can lead the analysis, but the review must belong to your organisation. The people who run the SEUs need to take part, agree the criteria and be able to explain the result to an auditor, because the review is updated long after any consultant has left.

Do the significant energy uses have to be at equipment level?

Not necessarily. An SEU can be a piece of equipment, a system, a process or a building, whichever level lets you measure it, identify its drivers and assign people to control it.

What does an auditor check in the energy review?

An auditor checks that the analysis rests on data, that the SEU criteria are written and applied consistently, that each SEU has relevant variables, current performance and named people, and that the opportunities and forecast flow into action plans and monitoring.

How often should the energy review be repeated?

At the interval you define, often once a year, and additionally whenever facilities, equipment, systems or energy-using processes change significantly. It helps to time the annual update so that its results reach the management review.

Who should take part in the energy review?

The energy management team leads it, with the engineers, operators and maintenance staff who run each candidate SEU, plus finance or purchasing for the invoice data.

ISO 50001 implementation

ISO 50001 requirements

Get the document

We e-mail the document as a PDF link. Tell us who you are and where to send it.

A quick security check confirms the request comes from a person.

By requesting the document you agree to our privacy notice. Sterling uses these details to send it and to respond to your request. We never sell your data.

Talk to a consultant

Ask how to build an energy review your engineers own and your auditor can test.

Tell us your goals, locations and target date. We’ll help you define the scope, timeline and next steps.

hello@sterling-grc.com

+1 201 263 4443 (global headquarters) · your nearest office and its number are at the top of this page

What would you like to achieve?

Choose a starting point. The enquiry form takes about a minute.

Your goal
Book my free discovery call

Continue to the enquiry form to share your details. Please do not include passwords, sensitive personal information or confidential files. A Sterling consultant replies within one working day. Privacy notice